QUINT4-UPS/1AC/1AC/500VA/USB - Uninterruptible power supply
1067327
QUINT AC-USV, IQ Technology, DIN rail mounting, input: 120 V AC / 230 V AC, output: 120 V AC / 230 V AC / 500 VA.
Input voltage 120 V AC
230 V AC
Input voltage range 90 V AC ... 264 V AC
Nominal input voltage range 100 V AC ... 240 V AC
Typical national grid voltage 120 V AC
Voltage type of supply voltage AC
Frequency range (fN) 45 Hz ... 65 Hz
Permissible backup fuse max. 25 A
Current consumption 6.9 A (100 V AC)
2.86 A (240 V AC)
19 A (24 V DC)
Efficiency > 97 % (100 % load, with charged energy storage)
~ 87 % (100 % load )
Apparent power 500 VA
Real power 400 W
Power factor (cos phi) 0.8
Crest factor 2.8
Switch-over time < 10 ms
UPS classification VFD-SS-311
Connection in parallel no
Connection in series No
Overload capability Mains operation in accordance with internal fuse
Overload capability Battery operation 105 % (Permanent)
120 % ... 150 % (20 s / 5 s, then shutdown)
Mains operation
Output voltage 120 V AC
230 V AC
Nominal output current (IN) 4.17 A (120 V AC)
2.17 A (230 V AC)
Maximum no-load power dissipation typ. 9 W (120 V AC)
typ. 10 W (230 V AC)
Power loss nominal load max. typ. 10 W (120 V AC)
typ. 11 W (230 V AC)
Nominal output frequency 60 Hz ±5 Hz
50 Hz ±5 Hz
Output fuse 10 A 400 V gRL
Battery operation
Output voltage 120 V AC ±2 %
230 V AC ±2 %
Form of output voltage Pure sine
Maximum no-load power dissipation approx. 23 W (120 V AC)
approx. 24 W (230 V AC)
Power loss nominal load max. approx. 57 W (120 V AC)
approx. 54 W (230 V AC)
Nominal output frequency 60 Hz
50 Hz
±5 % (grid-guided)
±0.5 % (self-guided)
Total harmonic distortion factor (THD) < 3 % (linear load)
< 8 % (non-linear load)
Electronic current limitation > 2,5 x IN (> 200 ms)
Input
Input voltage 24 V DC
Deep discharge protection 20 V DC ... 24 V DC (can be parameterized)
Nominal capacity range 3.4 Ah ... 200 Ah (5x 40 Ah)
Charging current max. 5 A
End-of-charge voltage 24 V DC ... 31 V DC (temperature compensated)
General
Battery technology VRLA, VRLA-WTR, LI-ION (see section: Ordering data)
Charge characteristic curve IU0U
Permissible backup fuse 50 A
Input
Position 1.x
Conductor connection
Connection method Screw connection
rigid 0.2 mm² ... 6 mm²
flexible 0.2 mm² ... 4 mm²
flexible with ferrule without plastic sleeve 0.2 mm² ... 4 mm²
flexible with ferrule with plastic sleeve 0.2 mm² ... 4 mm²
![QUINT4-UPS 1AC 1AC 500VA USB - Uninterruptible power supply](http://pic.1688club.com/1247/products/s_fca4f683ce3b76c659edd8301aff5922.jpg)