TTC-6P-3-HF-12DC-PT-I - Surge protection device
1065313
Surge protection, consisting of protective plug and base element, with integrated status indicator for three signal wires with common reference potential. For HF applications and telecommunications interfaces without supply voltage.
Product type Surge protection for information technology
Product family TERMITRAB complete
IEC test classification C1
C2
C3
D1
Type DIN rail module, two-section, divisible
Insulation characteristics
Overvoltage category III
Pollution degree 2
Nominal voltage UN 12 V DC
Connection method Push-in connection
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section rigid 0.2 mm² ... 4 mm²
Conductor cross section AWG 24 ... 12
Dimensional drawing
Width 6.2 mm +0.1 mm
Height 105.8 mm
Depth 100 mm (incl. DIN rail 7.5 mm)
Color (Base element) gray (RAL 7042)
Color (Male connector) light grey (RAL 7035)
Flammability rating according to UL 94 V-0
Insulating material PBT
Housing material PBT
Mechanical data
Open side panel No
Direction of action Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Maximum continuous voltage UC 15 V DC
10 V AC
Rated current 600 mA (56 °C)
Operating effective current IC at UC ≤ 100 µA
Residual current IPE ≤ 200 µA
Nominal discharge current In (8/20) µs (line-line) 5 kA
Nominal discharge current In (8/20) µs (line-ground) 5 kA
Pulse discharge current Iimp (10/350) µs (line-line) 0.5 kA
Pulse discharge current Iimp (10/350) µs (line-earth) 0.5 kA
Total discharge current Itotal (8/20) µs 10 kA
Voltage protection level Up (line-line) ≤ 145 V (C1 - 1 kV / 500 A)
≤ 260 V (C2 - 10 kV / 5 kA)
≤ 25 V (C3 - 25 A)
≤ 30 V (C3 - 100 A)
Voltage protection level Up (line-earth) ≤ 80 V (C1 - 1 kV / 500 A)
≤ 95 V (C2 - 10 kV / 5 kA)
≤ 25 V (C3 - 25 A)
≤ 30 V (C3 - 100 A)
Voltage protection level Up static (line-line) ≤ 40 V (C1 - 1 kV / 500 A)
≤ 95 V (C2 - 10 kV / 5 kA)
Voltage protection level Up static (line-earth) ≤ 40 V (C1 - 1 kV / 500 A)
≤ 95 V (C2 - 10 kV / 5 kA)
Response time tA (line-line) ≤ 1 ns
Response time tA (line-earth) ≤ 1 ns
Input attenuation aE, sym. typ. 0.3 dB (≤ 8.7 MHz / 150 Ω)
Input attenuation aE, asym. typ. 0.3 dB (≤ 10.5 MHz / 150 Ω)
Cut-off frequency fg (3 dB), sym. in 150 Ω system typ. 60 MHz
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ω system typ. 60 MHz
Capacity (Core-Core) typ. 32 pF
Capacity (Core-Earth) typ. 32 pF
Resistance per path 1.65 Ω ±20 %
Surge protection fault message optical
Max. required back-up fuse 630 mA (FF)
Impulse durability (line-line) C1 - 1 kV / 500 A
C2 - 10 kV / 5 kA
C3 - 100 A
Impulse durability (line-earth) C1 - 1 kV / 500 A