AXL E PN IOL8 DI4 M12 6M - Communication module
2701519
Axioline E, PROFINET, M12 connector, IO-Link ports Class A: 4, connection method: M12 connector, connection technology: 3-conductor, IO-Link ports Class B: 4, connection method: M12 connector, connection technology: 3-conductor, Digital inputs at pin 2 for class A ports: 4, 24 V DC, connection technology: 3-conductor, Metal housing, degree of protection: IP65/IP67
Width 60 mm
Height 185 mm
Depth 38 mm
Drill hole spacing 198.5 mm
Note on dimensions The height is 194.5 mm including the mounting panel. With fixing clips pulled out, the height is 212 mm. The depth is 38 mm including the mounting panel (30.5 mm without the mounting panel).
Housing material Zinc die-cast
PROFINET
Number of interfaces 2
Connection method M12 connector
Note on the connection method D-coded
Number of positions 4
Transmission speed 100 Mbps (with auto negotiation)
PROFINET
Equipment type PROFINET-Device
System-specific protocols PROFINET protocols LLDP
PROFINET protocols MRP client
PROFINET protocols DCP
PROFINET protocols DCE/RPC
Protocols supported SNMP v1
HTTP
TFTP
FTP
Digital:
Input name Digital inputs at pin 2 for class A ports
Description of the input IEC 61131-2 type 1
Number of inputs 4
Connection method M12 connector, X01 ... X04 have double occupancy
Connection technology 3-conductor
Input voltage range "0" signal -0.3 V DC ... 5 V DC
Input voltage range "1" signal 15 V DC ... 30 V DC
Nominal input voltage UIN 24 V DC
Nominal input current at UIN typ. 3 mA
Sensor current per channel max. 200 mA (from L+/L-)
Total sensor current max. 1.6 A (from L+/L-)
Input frequency 0.5 kHz
Input filter time < 1000 µs
Protective circuit Overload protection, short-circuit protection of sensor supply
Digital
Description of the input IO-Link ports in digital input (DI) mode
Number of inputs max. 8 (EN 61131-2 type 1)
Connection method M12 connector, X01 ... X04 have double occupancy
Connection technology 3-conductor
Nominal input voltage UIN 24 V DC
Input voltage range "0" signal -0.3 V DC ... 5 V DC
Input voltage range "1" signal 15 V DC ... 30 V DC
Nominal input current typ. 3 mA
Sensor current per channel max. 200 mA (from L+/L-)
Total sensor current max. 1.6 A (from L+/L-)
Input filter time < 1000 µs
Input frequency 0.5 kHz
Protective circuit Overload protection; yes
Short-circuit protection for the sensor supply; yes
IO-Link
Number of ports 4
Connection method M12 connector
Connection technology 3-conductor
Port type Class A
Cycle Time min. 2 ms (MasterCycleTime: PDInput* + PDOutput* + OnReqData* < = 17 Bytes, COM3; * see "IO-Link Interface and System Specification V1.1.2")
IO-Link
Number of ports 4
Connection method M12 connector
Connection technology 3-conductor
Port type Class B
Cycle Time min. 2 ms (MasterCycleTime: PDInput* + PDOutput* + OnReqData* < = 17 Bytes, COM3; * see "IO-Link Interface and System Specification V1.1.2")
Digital
Output description IO-Link ports in digital output (DO) mode
Connection method M12 connector, X01 ... X04 have double occupancy
![AXL E PN IOL8 DI4 M12 6M - Communication module](http://pic.1688club.com/1247/products/s_4e9098012b633dc92f00985269f98313.jpg)