AXL F BK EC - Bus coupler


  • Date:2024-05-22T02:30:33Z
    Price:Negotiation
    Company:上海当临自动化科技有限公司
    Place:China - Shanghai
    Address:上海市青浦区练西公路2850号1幢
    Contact:Jason(Manager)
    Contact Me:
    Tell:+86-19921425125
     Mobile:+86-19921425125
     Email:11155912443812134951185175@96qq4.13c33om

     Business License verifiedEmail verified

     

    AXL F BK EC - Bus coupler

    2688899

    Axioline F, Bus coupler, EtherCAT®, RJ45 jack, transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connector

    Width 45 mm
    Height 126.1 mm
    Depth 74 mm
    Note on dimensions The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715).

    EtherCAT®
    Number of interfaces 2
    Connection method RJ45 jack
    Note on the connection method Auto negotiation and autocrossing
    Transmission speed 100 Mbps (full duplex)
    Transmission physics Ethernet in RJ45 twisted pair
    Axioline F local bus
    Number of interfaces 1
    Connection method Bus base module
    Transmission speed 100 Mbps
    Service
    Number of interfaces 1
    Connection method USB type C (from HW 05)
    Micro USB type B (up to HW 04)
    Fieldbus: Local bus gateway
    Max. number of local bus devices 63 (Consider the logic current consumed by the devices)
    EtherCAT®
    System-specific protocols Mailbox protocols CAN application protocol over EtherCAT®
    Mailbox protocols File access over EtherCAT®
    Mailbox protocols Ethernet over EtherCAT®
    Mailbox protocols Safety over EtherCAT®
    Specification ETG.1000 V1.02

    System limits
    Number of supported devices max. 63 (per station)
    Number of local bus devices that can be connected max. 63

    Product type I/O component
    Product family Axioline F
    Type block modular
    Mounting position any (observe temperature derating)
    Scope of delivery including bus base module and Axioline F connector
    Diagnostics messages Emergency messages
    Messages via object 10F3hex Diagnosis history
    Insulation characteristics
    Overvoltage category II (IEC 60664-1, EN 60664-1)
    Pollution degree 2 (IEC 60664-1, EN 60664-1)

    Potentials: Communications power UL feed-in (the supply of the Axioline F local bus UBus is generated from UL)
    Supply voltage 24 V DC
    Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
    Current draw max. 570 mA (2.0 A at UBus, UL = 24 V, up to HW 04)
    max. 670 mA (2.5 A at UBus, UL = 24 V, from HW 05)
    Power consumption max. 13.7 W (2.0 A at UBus, UL = 24 V, up to HW 04)
    max. 16 W (2.5 A at UBus, UL = 24 V, from HW 05)
    Protective circuit Surge protection; electronic
    Reverse polarity protection; electronic
    Potentials: Axioline F local bus supply (UBus)
    Supply voltage 5 V DC (via bus base module)
    Power supply unit max. 2 A (up to HW 04)
    max. 2.5 A (from HW 05)
    Electrical isolation/isolation of the voltage ranges
    Test voltage: Ethernet interface 1 / Ethernet interface 2 1500 V AC, 50 Hz, 1 min.
    Test voltage: Ethernet interface 1 / 24 V communications voltage (UL) feed-in 1500 V AC, 50 Hz, 1 min.
    Test voltage: Ethernet interface 2 / 24 V communications voltage (UL) feed-in 1500 V AC, 50 Hz, 1 min.
    Test voltage: Ethernet interface 1 / functional ground 1500 V AC, 50 Hz, 1 min.
    Test voltage: Ethernet interface 2 / functional ground 1500 V AC, 50 Hz, 1 min.
    Test voltage: 24 V communications voltage (UL) feed-in / functional ground 500 V AC, 50 Hz, 1 min.

    Connection technology
    Connection name Axioline F connector
    Note on the connection method Please observe the information provided on conductor cross sections in the “Axioline F: system and installation” user manual.
    Conductor connection
    Connection method Push-in connection
    Conductor cross section rigid 0.2 mm² ... 1.5 mm²
    Conductor cross section flexible 0.2 mm² ... 1.5 mm²
    Conductor cross section AWG 24 ... 16
    Stripping length 8 mm

    AXL F BK EC - Bus coupler

Disclaimer:All information is provided by registered users. You may assess risks based on corresponding qualifications.