AXL F RTD4 1H - Temperature module
2688556
Axioline F, Temperature recording module, Analog inputs: 4 (for resistance temperature detectors), connection technology: 2-, 3-, 4-conductor (shielded), transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connectors
Width 35 mm
Height 126.1 mm
Depth 54 mm
Note on dimensions The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715).
Axioline F local bus
Number of interfaces 2
Connection method Bus base module
Transmission speed 100 Mbps
Module
Input address area 8 Byte
Output address area 8 Byte
Required parameter data 12 Byte
Required configuration data 6 Byte
Analog
Input name Analog inputs
Description of the input Inputs for resistive temperature sensors
Number of inputs 4 (for resistance temperature detectors)
Connection method Push-in connection
Connection technology 2-, 3-, 4-conductor (shielded)
A/D converter resolution 24 bit
Sensor types (RTD) that can be used Pt, Ni, KTY, Cu sensors
Data formats IB IL, S7-compatible
Measured value representation 16 bits (15 bits + sign bit)
Input filter time 40 ms
60 ms
100 ms
120 ms (adjustable)
Nominal value of the current sources 1 mA (Pt 100, Ni 100, RLin 500 Ω; pulse current, the specification is valid during the sampling phase)
210 µA (P t1000, Ni 1000, RLin 5000 Ω; pulse current, the specification is valid during the sampling phase)
Differential non-linearity typ. 1 ppm / ±0.0001 % (in all ranges)
Integral non-linearity typ. 30 ppm / ±0.003 % (Pt 100)
typ. 20 ppm / ±0.002 % (RLin 500 Ω)
typ. 200 ppm / ±0.02 % (RLin 5000 Ω)
Linear resistance measuring range 0 Ω ... 500 Ω
0 kΩ ... 5 kΩ
Protective circuit Short-circuit protection, overload protection of the inputs
Transient protection of inputs
Transient protection of sensor supplies
Product type I/O component
Product family Axioline F
Type block modular
Mounting position any (no temperature derating)
Scope of delivery including bus base module and Axioline F connectors
Insulation characteristics
Overvoltage category II (IEC 60664-1, EN 60664-1)
Pollution degree 2 (IEC 60664-1, EN 60664-1)
Potentials
Power consumption max. 1.1 W (at UBus and UA)
Potentials: Axioline F local bus supply (UBus)
Supply voltage 5 V DC (via bus base module)
Current draw max. 140 mA
Power consumption max. 700 mW
Potentials: Supply for analog modules (UA)
Supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw max. 17 mA
Power consumption max. 400 mW
Protective circuit Surge protection; electronic (35 V, 0.5 s)
Reverse polarity protection; Polarity protection diode
Transient protection; Suppressor diode
Electrical isolation/isolation of the voltage ranges
Test voltage: 5 V supply of the local bus (UBus) / 24 V supply (I/Os) 500 V AC, 50 Hz, 1 min.
Test voltage: 5 V supply of the local bus (UBus)/analog inputs 500 V AC, 50 Hz, 1 min.
Test voltage: 5 V supply of the local bus (UBus) / functional ground 500 V AC, 50 Hz, 1 min.
Test voltage: 24 V supply (I/O)/analog inputs 500 V AC, 50 Hz, 1 min.
Test voltage: 24 V supply (I/O) / functional ground 500 V AC, 50 Hz, 1 min.
Test voltage: Analog inputs/functional ground 500 V AC, 50 Hz, 1 min.
![AXL F RTD4 1H - Temperature module](http://pic.1688club.com/1247/products/s_4966e5cc5bade08728203975049eadfe.jpg)