IB IL AI/TEMP 4 RTD-PAC - Analog module
2897952
Inline, Analog input terminal, 0 V ... 10 V, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connectors and marking fields
The terminal is designed for use within an Inline station. The terminal has four inputs that can be configured independently of one another for measuring voltages or resistances or for RTDs. The sensors are connected using 2-conductor technology, so that a nominal resistance of at least 1000 Ω is recommended when sensors with a relatively small temperature coefficient (e.g., platinum sensors) are used. Resistance measurement with conversion into temperature values can be used for temperature measurement with NTC resistors. The advantage of these resistors is their large temperature coefficient.
Width 12.2 mm
Height 140.5 mm
Depth 71.5 mm
Utilization restriction
EMC note EMC: class A product, see manufacturer's declaration in the download area
Inline local bus
Connection method Inline data jumper
Transmission speed 500 kbps
Transmission physics Copper
Module
ID code (dec.) 95
ID code (hex) 5F
Length code (hex) 02
Length code (dec) 02
Process data channel 32 bit
Input address area 4 Byte
Output address area 4 Byte
Register length 32 bit
Required parameter data 1 Byte
Required configuration data 5 Byte
Analog:
Voltage input signal 0 V ... 10 V
Data formats IB IL, IB ST, standardized representation, S7 compatible
Filtering None or mean-value generation over 8 or 32 measured values
Limit frequency (3 dB) 6.6 Hz
Measured value resolution 16 bits (15 bits + sign bit)
Analog
Input filter time 150 ms
1200 ms
4800 ms (adjustable)
Linear resistance measuring range 0 Ω ... 3 kΩ
0 Ω ... 300 kΩ
Product type I/O component
Product family Inline
Type modular
Scope of delivery including Inline connectors and marking fields
Insulation characteristics
Overvoltage category II (IEC 60664-1, EN 60664-1)
Pollution degree 2 (IEC 60664-1, EN 60664-1)
Potentials: Communications power (UL)
Current draw max. 65 mA
Connection technology
Connection name Inline connector
Conductor connection
Connection method Spring-cage connection
Conductor cross section rigid 0.08 mm² ... 1.5 mm²
Conductor cross section flexible 0.08 mm² ... 1.5 mm²
Conductor cross section AWG 28 ... 16
Stripping length 8 mm