ELR W3-230AC/500AC- 9I - Hybrid motor starter
2297060
Hybrid motor starter for reversing 3~ AC motors up to 500 V AC and 9 A output current, with 230 V AC control voltage, adjustable overload shutdown, emergency stop function up to SIL 3/PL e, and screw connection
Product type Hybrid motor starters
Product family CONTACTRON
Operating mode 100% operating factor
Number of phases 3
Motor starter type Reversing starter
Maximum power dissipation for nominal condition 13.5 W
Switching frequency ≤ 2 Hz (Load-dependent)
Maximum power dissipation 16.1 W
Minimum power dissipation 2.6 W
Supply
Rated control circuit supply voltage US 230 V AC
Control supply voltage range 92 V AC ... 253 V AC
Rated control supply current IS 4 mA
Mains frequency 40/100 Hz
Protective circuit Surge protection
Insulation characteristics
Rated insulation voltage 500 V
Rated surge voltage 6 kV
Overvoltage category III
Degree of pollution 2
Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit Safe isolation (IEC 60947-1) at operating voltage ≤ 300 V AC
Basic insulation (IEC 60947-1) at operating voltage 300 V AC ... 500 V AC
Isolation characteristics between the control input and control supply voltage to auxiliary circuit Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
Control
Input name Control input right/left
Rated actuating voltage UC 230 V AC
Triggering voltage range 92 V AC ... 253 V AC
Rated actuating current IC 7 mA
Switching threshold 44 V AC (“0” signal)
85 V AC (“1” signal)
Switching level < 5 V DC (For EMERGENCY STOP)
Typical response time < 35 ms
Typical turn-off time < 80 ms
AC output
Rated operating voltage Ue 500 V AC
Operating voltage range 42 V AC ... 550 V AC
Rated operating current Ie 9 A (AC-51)
6.5 A (AC-53a)
Mains frequency 50/60 Hz
Load current range 1.5 A ... 9 A (see to derating)
Trigger characteristic in acc. with IEC 60947-4-2 Class 10A
Cooling time 20 min. (for auto reset)
Leakage current 0 mA
Residual voltage < 0.5 V
Surge current 100 A (t = 10 ms)
Protective circuit Surge protection
Acknowledge output
Note Confirmation: floating change-over contact, signal contact
Contact switching type 1 changeover contact
Switching capacity in accordance with IEC 60947-5-1 3 A (230 V, AC15)
2 A (24 V, DC13)
Residual voltage < 0.5 V
Control circuits
Connection method Screw connection
Stripping length 8 mm
Screw thread M3
Conductor cross section rigid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 14
Tightening torque 0.5 Nm ... 0.6 Nm
5 lbf-in. ... 7 lbf-in.
Load circuit
Connection method Screw connection
Stripping length 8 mm
Screw thread M3
Conductor cross section rigid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 14
Tightening torque 0.5 Nm ... 0.6 Nm
5 lbf-in. ... 7 lbf-in.
Status display Yellow LED
Operating voltage display Green LED
Error indication Red LED
Width 22.5 mm
Height 107 mm
Depth 114 mm
Flammability rating according to UL 94 V0 (Housing)