IB IL 24/48 DOR 2/W-PAC - Relay Module
2863119
Inline, Relay terminal, Relay outputs: 2 (floating), Changeover contact, 24 V AC, 48 V DC, for switching ohmic loads, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connector and labeling field
The terminal is designed for use within an Inline station. It has two floating SPDT relay contacts, which are independent of one another.
Dimensional drawing
Width 12.2 mm
Height 119.8 mm
Depth 71.5 mm
Note on dimensions Housing dimensions
Inline local bus
Number of interfaces 2
Connection method Inline data jumper
Transmission speed 500 kbps
Module
ID code (dec.) 189
ID code (hex) BD
Length code (hex) C2
Length code (dec) 194
Process data channel 2 bit
Input address area 0 bit
Output address area 2 bit
Register length 2 bit
Required parameter data 3 Byte
Required configuration data 4 Byte
Relay
Number of outputs 2 (floating)
Connection method Spring-cage connection
Contact switching type Changeover contact
Switching voltage min. 10 mV (DC)
max. 30 V AC (PELV (EN 61131))
max. 60 V DC (PELV (EN 61131))
Switching current min. 10 µA
max. 2 A (30 V DC)
max. 1 A (60 V DC)
Switching capacity 60 W
62 VA (ohmic)
Limiting continuous current 2 A (at maximum ambient temperature)
Mechanical service life 2x 105 cycles
Product type I/O component
Product family Inline
Type modular
Scope of delivery including Inline connector and labeling field
No. of channels 2
Operating mode Process data mode with 2 bits
Special properties for switching ohmic loads
Insulation characteristics
Overvoltage category II (IEC 60664-1, EN 60664-1)
Pollution degree 2 (IEC 60664-1, EN 60664-1)
Potentials: Communications power (UL)
Supply voltage 7.5 V DC (via voltage jumper)
Current draw max. 30 mA
Power consumption max. 0.23 W
Potentials: Segment circuit supply (US)
Supply voltage 24 V DC (via voltage jumper)
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw max. 4 A
Electrical isolation/isolation of the voltage ranges
Test voltage: Relay contact / Bus logics 1.5 kV, 50 Hz, 1 min.
Test voltage: Contact/contact 1 kV, 50 Hz, 1 min.
Test voltage: Contact/functional ground 1 kV, 50 Hz, 1 min.
Connection technology
Connection name Inline connector
Conductor connection
Connection method Spring-cage connection
Conductor cross section rigid 0.08 mm² ... 1.5 mm²
Conductor cross section flexible 0.08 mm² ... 1.5 mm²
Conductor cross section AWG 28 ... 16
Stripping length 8 mm