IB IL 24 DO 16-PAC/SN - Digital module
2862961
Inline, Digital output terminal, Digital outputs: 16, 24 V DC, 500 mA, connection technology: 3-conductor, transmission speed in the local bus: 500 kbps, degree of protection: IP20, including Inline connectors and marking fields, connectors numbered individually
Width 48.8 mm
Height 140.5 mm
Depth 71.5 mm
Note on dimensions Housing dimensions
Utilization restriction
CCCex note Use in potentially explosive areas is not permitted in China.
Inline local bus
Number of interfaces 2
Connection method Inline data jumper
Transmission speed 500 kbps
Module
ID code (dec.) 189
ID code (hex) BD
Length code (hex) 01
Length code (dec) 01
Process data channel 16 bit
Input address area 0 Byte
Output address area 2 Byte
Register length 16 bit
Required parameter data 4 Byte
Required configuration data 4 Byte
Digital:
Output name Digital outputs
Connection method Spring-cage connection
Connection technology 3-conductor
Number of outputs 16
Protective circuit Overload protection, short-circuit protection of outputs; electronic
Output voltage 24 V DC (US - 1 V)
Limitation of the voltage induced on circuit interruption -46 V ... -15 V
Maximum inrush current max. 1.5 A (at nominal lamp load for 20 ms)
Output current max. 500 mA (per channel)
max. 8 A (Device)
Nominal output voltage 24 V DC
Output voltage when switched off max. 2 V
Output current when switched off max. 300 µA
Nominal load, inductive 12 W (1.2 H, 48 Ω)
Nominal load, lamp 12 W
Nominal load, ohmic 12 VA (48 Ω)
Maximum operating frequency with ohmic nominal load max. 300 Hz (this switching frequency is limited by the number of bus devices, the structure of the bus, the software used and the control or computer system used)
Reverse voltage resistance to short pulses Reverse voltage proof
Behavior with overload Auto restart
Behavior with inductive overload Output can be destroyed
Behavior at voltage switch-off The output follows the power supply without delay
Overcurrent shut-down min. 0.7 A
Output current with ground connection interrupt when switched off max. 25 mA
Product type I/O component
Product family Inline
Type modular
Scope of delivery including Inline connectors and marking fields, connectors numbered individually
No. of channels 16
Operating mode Process data mode with one word
Diagnostics messages Short-circuit or overload of the digital outputs Error message in the diagnostic code (bus) and display (2 Hz) via the LED (D) on the module
Insulation characteristics
Overvoltage category II (IEC 60664-1, EN 60664-1)
Pollution degree 2 (IEC 60664-1, EN 60664-1)
Potentials: Communications power (UL)
Supply voltage 7.5 V DC (via voltage jumper)
Current draw max. 90 mA
Power consumption max. 0.675 W
Potentials: Segment circuit supply (US)
Supply voltage 24 V DC (via voltage jumper)
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw max. 8 A