    EC-E1 12A - Electronic circuit breaker

    0903031

    Electronic circuit breaker, signal contact: 1 N/O contact, nominal current: 12 A

    General When mounted in rows without convection cooling, the nominal device current should only be led to a maximum of 80% due to the thermal effect during continuous operation (100% operating factor).
    Special precautionary measures must be taken in systems or machines, to prevent components from restarting (e.g., use of a safety PLC).
    Parallel connection of multiple circuit breakers is not permitted.

    Product type Device circuit breakers
    Product family EC-E
    Type DIN rail module, one-piece
    Number of positions 1
    No. of channels 1
    Insulation characteristics
    Degree of pollution 2

    Fuse type Automatic device
    Maximum power dissipation for nominal condition ≤ 2.16 VA
    Switching capacity ICN Active current limitation
    Fuse electronic
    General
    Operating voltage 24 V DC
    18 V DC ... 32 V DC
    Nominal current IN 12 A
    Rated surge voltage 0.5 kV
    Tripping method E (electronic)
    Required backup fuse not required, integrated failsafe element
    Dielectric strength max. 32 V DC (Load circuit)
    Switch off Typ. 1.8 x IN
    Active current limitation active
    Fuse electronic
    Closed-circuit current range I0 typ. 25 mA ±5 mA (When switched on)
    MTBF (IEC 61709, SN 29500) 7430000 h (at 25 °C with 80 % load)
    6590000 h (at 40 °C with 80 % load)
    Voltage drop 180 mV (at IN)
    Load circuit
    Max. capacitive load 20000 µF
    Auxiliary contact
    Contact connection type floating signal contact
    Minimum operating voltage Umin DC 10 V DC
    Maximum operating voltage Umax DC 30 V DC
    Minimum operating current Imin 10 mA
    Max. operating current Imax 0.5 A
    Indicator/remote signaling
    Connection name Auxiliary contact
    Switching function N/O contact

    Nominal cross section 16.00 mm²
    Line+ / LOAD+ /0V
    Screw thread M4
    Tightening torque ... 1.2 Nm
    Stripping length 10 mm
    Conductor cross section rigid 0.5 mm² ... 16 mm²
    Cross section AWG 20 ... 6 (converted acc. to IEC)
    Conductor cross section flexible 0.5 mm² ... 16 mm²
    Conductor cross section, flexible [AWG] 20 ... 6 (converted acc. to IEC)
    Conductor cross-section flexible (ferrule without plastic sleeve) 0.5 mm² ... 10 mm²
    Flexible conductor cross section (ferrule with plastic sleeve) 0.5 mm² ... 10 mm²
    2 conductors with same cross section, solid 0.5 mm² ... 4 mm²
    2 conductors with the same cross-section AWG rigid 20 ... 12 (converted acc. to IEC)
    2 conductors with same cross section, flexible 0.5 mm² ... 4 mm²
    2 conductors with the same cross-section AWG flexible 20 ... 12 (converted acc. to IEC)
    2 conductors with same cross section, flexible, with ferrule without plastic sleeve 0.5 mm² ... 2.5 mm²
    2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve 0.5 mm² ... 6 mm²
    Nominal cross section 16 mm²
    Auxiliary contact
    Screw thread M3
    Tightening torque ... 0.5 Nm
    Stripping length 8 mm
    Conductor cross-section flexible (ferrule without plastic sleeve) 0.25 mm² ... 2.5 mm²
    Flexible conductor cross section (ferrule with plastic sleeve) 0.25 mm² ... 2.5 mm²
    Line+/LOAD+/0V
    Connection method Screw connection
    Screw thread M4
    Tightening torque 1.2 Nm

    EC-E1 12A - Electronic circuit breaker